208/230V 1000VA 900W Double-Conversion UPS - 6 Outlets, Extended Run, WEBCARDLX, LCD, USB, DB9, 2U
Product Name |
Eaton Tripp Lite series SmartOnline UPS
|
Catalog Number |
SUINT1000LCD2UN
|
Product Length/Depth |
23.5 in
|
Product Height |
9.6 in
|
Product Width |
19.8 in
|
Product Weight |
28 lb
|
Compliances |
RoHS
CE Marked EAC ENERGY STAR certified SASO |
Certifications |
CSA certified
NOM UL 1778 |
Topology |
Online/Double-conversion
|
Form factor |
Rackmount
|
Rack size |
2U
|
Package contents |
|
Current Crest Ratio |
3:1
|
Input nominal voltage |
200 VAC/208 VAC/220 VAC/230 VAC/240 VAC
|
Input frequency range |
|
Receptacle |
|
Battery replacement |
RBC24S
|
Runtime at half load |
12.3 min
|
Noise level |
<45 dB at 1 meter
|
Relative humidity |
5-95% non-condensing
|
Front Panel LCD Display |
Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options
|
Output Receptacles |
C13
|
Product Features |
Individually Controllable Load Banks
Expandable Runtime |
Product Highlights |
Offers network-grade protection against power failures and voltage fluctuations
Zero transfer time between on-line and battery modes for uninterrupted operation Optional external battery packs provide additional runtime for applications requiring it Pre-installed WEBCARDLXE with latest version of PADM20 supports Auto Probe feature ENERGY STAR-certified to save electricity, lower costs, and protect the environment |
PowerAlert Software |
Free download from https://tripplite.eaton.com/products/power-alert
|
Network Management Cards |
WEBCARDLXE
|
Network Management Cards Details |
Network management card included
|
Output power factor |
0.9
|
Phase (input) |
Single-phase
|
Runtime at full load |
4.7 min. (900W)
|
Communication interface |
DB9 Serial
Contact closure EPO (emergency power off) USB (HID enabled) Slot for SNMP / Web interface Pre-installed network card |
Battery Access |
Front panel battery access door
|
Typical Battery Runtime |
Expandable Runtime
|
Dc Voltage |
24
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Communications Cable |
USB and DB9 cabling included
|
Grounding Details |
Back panel grounding lug included
|
Included Output Power Cables |
Includes 2 C13 to C14 power cables
|
Optional Mounting Accessory Notes |
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
|
Load Management Receptacles |
Two switchable 2-outlet load banks
|
High Voltage Transfer to Battery Power |
288V
|
Low Voltage Transfer to Battery Power |
160V (100% load), 140V (66% load), 120V (33% load)
|
Undervoltage Correction |
2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load)
|
Application |
Mission Critical Applications
|
Switch configuration |
5 front panel switches: On/Off, Up, Down and Escape
|
AC suppression joule rating |
627
|
Housing material |
Metal
|
Output AC waveform (AC mode) |
Pure Sine wave
|
Output AC waveform (battery mode) |
Pure sine wave
|
Output Capacity (kVA) |
1
|
Output Capacity (kW) |
0.9
|
Output Capacity (VA) |
1000
|
Output Capacity Details |
DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 630 watts for 208/220/230/240V output voltages; Max output is 720W (504W in Frequency Conversion mode) at 200V output voltage
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).
|
Primary UPS Depth (mm) |
397
|
Primary UPS Height (mm) |
88
|
Primary UPS Width (mm) |
438
|
AC Suppression Response Time |
Instantaneous
|
Alarm Interface |
Power-fail alarm can be silenced by following on-screen prompts
|
Audible Alarms |
Audible alarm indicates power failure, low battery, overload and fault
|
Battery Start Capability |
Cold-start operation supported
|
Cooling Method |
Fan
|
Battery Replacement Description |
Hot-swappable, replaceable batteries
|
LED Indicators |
4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red)
|
Frequency Rating Details |
Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation
|
Minimum Required Rack Depth With External Battery Pack |
18.75
|
Minimum Required Rack Depth Without External Battery Pack |
18
|
Output Voltage Regulation (Economy Line Mode) |
+/- 10%
|
Output Voltage Regulation (Line Mode) |
+/- 2%
|
Output Voltage Regulation(Battery Mode) |
+/- 2%
|
Overvoltage Correction |
2% output voltage regulation during overvoltages to 288V
|
Rechargeable Battery |
Less than 4.1 hours from 10% to 90% (typical, full load discharge)
|
Storage Temperature |
5° to 122°F (-15° to 50°C)
|
Included Mounting Accessory Description |
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
|
Nominal Voltage Details |
Nominal output voltage is user configured on first power-on
|
Voltage Regulation Description |
Online, double-conversion power conditioning
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications
|
Maximum Input Amps |
5
|
Minimum Required Rack Depth (cm) |
48.26
|
Minimum Required Rack Depth (inches) |
19
|
UPS Dataline Suppression Details |
Single line dialup / network dataline protection included
|
UPS Power Module Dimensions |
3.46 x 17.24 x 15.63
|
Power Mode Transfer Time |
0 ms
|
Optional Accessories |
2 post rackmount (2POSTRMKITWM)
2-4 post front rail rackmount (UPSHDEARKIT) 4 post rackmount short-depth (4POSTRAILKITWM) Tower (2-9USTAND) Wallmount (2POSTRMKITWM) |
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
C14 inlet
|
External Battery Pack Compatibility |
BP24V15RT2U (limit 1)
BP24V70-3U (multi-pack compatible) |
Green Energy-Saving Features |
High efficiency economy mode operation
Individually controllable load banks |
High Availability UPS Features |
Surge/noise protection
Auto probe monitoring and reboot (included) Zero transfer time Automatic inverter bypass Remote management Hot swappable batteries |